Chilled-Water System

In a chilled-water system the air conditioner cools water to between 40 and 45oF (4 and 7oC). The chilled water is distributed throughout the building in a piping system and connected to air condition cooling units wherever needed.
Total Heat Removed

The total heat removed by air condition chilled-water installation can be expressed as

h = 500 q dt (1)
where
h = total heat removed (Btu/h)
q = water flow rate (gal/min)
dt = temperature difference (oF)

Evaporator Flow Rate
The evaporator water flow rate can be expressed as
qe = htons 24 / dt (2)
where
qe = evaporator water flow rate (gal/min)
htons = air condition cooling load (tons)

Condenser Flow Rate
The condenser water flow rate can be expressed as
qc = htons 30 / dt (2)
where
qc = condenser water flow rate (gal/min)
htons = air condition cooling load (tons)